Model Simplication and Calculation Method Analysis About the Shunt of DC Grounding Current Via AC Grid

Zhi-chao REN,Guang-ning WU,Wei ZHEN,Chao WU,Yi-kun ZHANG
DOI: https://doi.org/10.13336/j.1003-6520.hve.2011.04.030
2011-01-01
Abstract:The calculation about the shunt of DC grounding current via AC grid is a complex process,involving a large range of geological hierarchical structure.To simplify the calculation model so as to put forward the relationship of the DC earth potential distribution and the shunt of DC grounding current,firstly,we analyzed the Hummel method by applying soil-layer structure simplification and its impact to the grounding potential distribution;secondly,we studied the law of the DC earth potential distribution and the characteristic of the shunt of DC grounding current;finally,we discussed the composition of equivalent resistance in the DC Pathway,and put forward the calculation method of DC earth potential.The results show that: the method of simplification layer can be adopted to calculate DC earth potential when the distance between substaions and DC grounding electrode is far enough.The distortion will occur nearby the grounding network in a small range,and the existence of AC transmission line will decrease the difference value of DC earth potential between the connected sites.The grounding current into the earth and complicated earth stratified resistant can be equivalent to the voltage source and power internal resistance.While solving the electromotive force of equivalence voltage source,attenuation cosine equivalent form of Bessel function can replace infinite progression.
What problem does this paper attempt to address?