Optimal Design of Grounding Grid in Which Conductor Unequally Spaced

左鹏,魏冲,邹军,袁建生
DOI: https://doi.org/10.13336/j.1003-6520.hve.2011.09.023
2011-01-01
Abstract:In order to decrease the maximum touch voltage,the layout of the grounding conductors was studied when the total length of grounding conductor was not changed.By analyzing the percentage of the conductor spaces in optimal layout,the Gaussian function distribution of grounding conductors was proposed.The Gaussian function layout method of grounding conductors was that the conductor spaces of grounding grid from edge to center were obtained from Gaussian function.Compared with the optimal compression ratio distribution,the maximum touch voltage was decreased by ten percent.The Gaussian function distribution of conductors could meet the basic requirements of safety and the minimal cost.Results were obtained under the condition of uniform soil,and the optimal layout of grounding grid conductors in multi-layer soil could be obtained by the similar method.