Indirect One Cycle Current Control Strategy of Z Source Grid-Connected Inverter

HOU Shi-ying,XIAO Xu,ZHANG Chuang,HUANG Zhe
DOI: https://doi.org/10.3969/j.issn.1007-449x.2011.09.004
2011-01-01
Abstract:Because of needing more sampling sectors,the direct current control method had disadvantages of complex control circuit,and the control accuracy depended on the accuracy of the sensor,so the indirect one cycle current control method with no current sampling sensor was proposed.Targeting on the single phase Z source grid-connected inverter,analyzing its steady-state mathematical model and deriving the duty cycle control function d(t) with the goal of realizing grid-connecting with unit power factor,then based on the ideas of one cycle control,the corresponding switch drive signal was generated according to d(t),finally the grid current was controlled.Simulation results show that the output current of the inverter has the same frequency and phase with the grid voltage,and can change according to changes in input power.In this control method,the structure of the control circuit is very simple and the cost is low,while this method is based on the average model state of the system,the shortcomings of slow dynamic response of the traditional amplitude and phase control strategy is overcome;in addition,the use of one cycle control also ensures the system have good robustness.