Polarized Current Travelling-wave Based Directional Relay

王世勇,董新洲,施慎行
DOI: https://doi.org/10.7500/AEPS20131114015
2011-01-01
Abstract:Capacitor voltage transformer cannot transmit wide frequency band voltage fault travelling-waves effectively,so that traditional voltage fault travelling-wave based directional relay cannot be applied to power system protections.Then a polarized current travelling-wave based directional relay(PCTDR) for transmission lines is put forward.This directional relay judges the fault direction by comparing the initial polarity of fundamental frequency components in voltage fault transient travelling-waves with the wave front polarity of current fault initial travelling-wave.This method resolves the problems that the traditional travelling-wave directional relay cannot be utilized in power system because capacitor voltage transformer cannot transmit wide frequency band voltage travelling-waves effectively.The basic principle and protection algorithm of PCTDR are presented.Simulation model of a 750 kV transmission system has been constructed with alternative transient program(ATP).Simulation results verify that PCTDR has good operation performance because it has fast operation speed and is immune to fault types,fault distance,fault path resistance and current transformer saturation. This work is supported by the National Natural Science Foundation of China(No.50937003,No.51007045),the Foundation of State Key Lab of Power Systems of China(No.SKLD09M04),National Key Technology Research and Development Program of China(No.2006BAJ16B02),and Specialized Research Fund for the Doctoral Program of Higher Education of China(No.200800031034).
What problem does this paper attempt to address?