Structural Performance Analysis of a Cooling-Tower Shell with Meridional Geometric Imperfections

肖南,苗永志,赵文争
DOI: https://doi.org/10.3785/j.issn.1008-973x.2010.04.033
2010-01-01
Abstract:The reinforced concrete hyperbolic cooling tower may have geometric imperfections,which stem from construction errors,the effect of creep/shrinkage of concrete,service loads,and so on.In order to investigate the influence of meridional geometric imperfections on hyperbolic cooling towers,two models,the perfect model and the constructed model,were analyzed by software ANSYS under various load cases to illustrate the structural performance,such as dynamic characteristics,static behaviors and stability.The results reveal that,the meridional geometric imperfections increase the lateral stiffness,enlarge the primary natural frequency and reduce the displacement under horizontal loads.In the vicinity of imperfections,stress concentration phenomenon is found under wind load or self-weight.In addition,according to the results of load combination,both hoop forces and meridional bending moments are augmented while hoop bending moments and meridional forces vary slightly.And temperature-induced structural performance is not sensitive to the imperfections.From the formulation in the national code,the local elastic buckling factor of the shell is reduced remarkably.Meanwhile,eigenvalue buckling analysis reflects that the buckling factor is increased under wind load while reduced under self-weight,i.e.,the deviation of hyperbolic curve produces different buckling features due to different kinds of loads.
What problem does this paper attempt to address?