Experimental Analysis of On-site Calibration of Electronic Instrument Transformer

Hong-en TAN,Hao-liang HU,Min LEI,Shu-han ZHANG,Qian LI,He LI,Deng-yun LI
DOI: https://doi.org/10.13336/j.1003-6520.hve.2010.12.021
2010-01-01
Abstract:In order to guarantee the safe and reliable performance of the electronic instrument transformers in power system, on-site calibration for electronic instrument transformers are needed. We introduced the basic principle and characteristics of the active and passive electronic instrument transformers, and proposed an electronic instrument transformers calibration system based on the direct digital calibration method. In addition, an on-site calibration for electronic instrument transformers in a 110 kV digital substation was experimentally researched by using the calibration system. Experimental results show that, electronic instrument transformers with analog output type have deviations of 20 minutes in phase error and 0.2% in ratio error at different test points; the outputs of passive electronic current transformers contain much signal burrs when the setting current is small; the active electronic instrument transformers output large DC component. Therefore, to ensure the overall energy metering accuracy, proper test points should be chosen for the on-site calibrations of electronic instrument transformers, and the corresponding inspection standards for the new features should also be established.