An Approach to Suppress Lightning Overvoltage of Transformer by High Frequency Magnetic Ring with Paralleled Damping Resistance

GUAN Yonggang,LIAO Fuwang,YUE Gongchang,HUANG Haikun,LIU Weidong,LIN Haiyuan
DOI: https://doi.org/10.13335/j.1000-3673.pst.2010.09.017
2010-01-01
Abstract:In view of the fact the arrester can only suppress the magnitude,but not the steepness,of a lightning overvoltage,so the failures of power transformers due to lightning overvoltage happen occasionally.The authors propose an approach to suppress lightning overvoltage of transformers located in substations by means of high-frequency magneitc rings,which connect in parallel with damping resistor,in series with transmission line in appropriate position.Through the test and simulation of oscillation circuit,an EMTP model to simulate and calculate high-frequency magnetic rings is built.Simulation and calculation results of a certain actual 220 kV substation show that by means of choosing proper material as well as proper shape and size for magnetic rings,the proposed approach can effectively suppress the amplitude of lightning overvoltge and alleviate its steepness,thus it can be used as a supplementary measure to the arresters.
What problem does this paper attempt to address?