Power Converse in Multi-Infeed HVDC System

杨光亮,邰能灵,郑晓冬,傅坚
DOI: https://doi.org/10.3969/j.issn.1006-6047.2010.05.005
2010-01-01
Abstract:When fault occurs at the inverter side of HVDC power system,the power converse of power lines near converter station may happen. The causes and solutions of the traditional power converse are introduced and the AC-DC interconnected power system model is established with EMTDC for the multi-infeed HVDC system. The faults occurred at the AC side of inverter stations and of the HVDC transmission lines are analyzed,which shows that,if severe fault occurs at the AC side of the multi-infeed HVDC system,especially when the fault distance is short,it may lead to the commutation failure in both converter stations simultaneously,the power converse of AC lines adjacent to inverter stations and the misoperation of pilot protection. In general,the fault of HVDC transmission line is unlikely to cause the power converse. The mechanism of power converse caused by commutation failure is presented:the demand of reactive power during fault recovery increases rapidly. Practical solutions to pilot protection misoperation are put forward.