EXPERIMENTAL STUDIES ON THE OPERATION OF AIR SOURCE HEAT PUMP IN EXTREME WINTER WEATHER

Yinlin Xiao,Cheng Zhang,Xiangzhao Fu
2010-01-01
Abstract:The operating performance of air source heat pump on snowy days for a residence in hot summer and cold winter areas was tested; the results show that when comparing to the rated heating capacity, the average of heating capacity falls 15% and the droop rate of the maximum instantaneous valve can be up to 30%. The average COP of heating conditions was 2.66 with a droop rate of 11.3% relative to the rated COP. The average COP of operation cycle containing defrosting was 2.37 with a droop rate of 20.9% relative to the rated COP. Power consumption of defrosting was 9.2% of the total power consumption. Without defrosting, the maximum of the instantaneous heating capacity was almost 94%~98% of the rated valve. Heating capacity changes caused by different wind speeds of indoor unit was about 4%. It's proved that outdoor unit working in the frosting condition is the main reason of heating capacity and COP declining. The advanced defrosting measure is the key to diminish the influence of frosting and improve the operating efficiency.