Low Voltage Ride-through Control of Doubly-fed Induction Generator Wind Turbines with a Series Grid-side Converter

YAO Jun,LIAO Yong,LI Hui
2010-01-01
Abstract:Doubly-fed induction generator (DFIG) is sensitive to the grid faults, and its low voltage ride-through (LVRT) operation and control technology attracts more and more research interests. The LVRT operation characteristics of doubly-fed induction generator wind turbines with a series grid-side converter in the stator are investigated, and an operational control strategy is proposed. To restrain the stator and rotor currents during the grid fault, the series grid-side converter is controlled to suppress the transient DC flux component in the stator flux and the negative component in the grid voltage. In the mean time, a successful LVRT under the grid fault is realized by also controlling the rotor-side converter. Simulation results show that the proposed control strategy can make the DFIG system achieve zero voltage ride-through, and the generation system with the new topology has the excellent fault ride-through capability under symmetrical and unsymmetrical faults. ©2010 State Grid Electric Power Research Institute Press.