Development of a Nanosecond Plused Magnetic Field Sensor

Ke-dao LIANG,Yan MI,Cheng-xiang LI,Chen-guo YAO,Cai-xin SUN,Peng TIAN
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.08.047
2009-01-01
Abstract:The switching operation in the primary circuit will cause the electromagnetic transient process in the highvoltage bus,which produces the transient voltage in the secondary side of the potential transformer and consequently causes the interference in the secondary circuit.All the interferences can cause problems like misoperation,data loss,damage of equipments etc.In order to evaluate the transient electromagnetic interference in substations and to analyze the contributions of shielding measures to the interference,based on Faraday's law of electromagnetic induction,we developed a pulsed magnetic field sensor which could be used to measure fast transient magnetic pulses with ns rise time,high amplitude,broadband.The sensor basic principles,amplitude frequency characteristics,sensitivity,amplitude response for square wave magnetic and interference in measurements were analyzed, calibrated and tested by a electromagnetic pulse simulator,and its design approach and problems that should be paid attention to during development were also discussed.The results show that this sensor' sensitivity is 703.42 V/T.and its frequency band is 400 kHz~1 00 MHz.That is to say it can meet the requirements of measurement of transient pulsed magnetic field in substations.
What problem does this paper attempt to address?