Control Strategy of Grid-Connected Converter Without AC Voltage Sensor and Its Improvement

吴凤江,孙秀冬,孙力,赵克
DOI: https://doi.org/10.3969/j.issn.1006-6047.2009.07.007
2009-01-01
Abstract:The DPC(Direct Power Control) strategy based on VF(Virtual Flux-linkage) is applied to grid-connected converter.The functions between VF and instantaneous power are derived.As the instantaneous powers can be obtained without grid-side voltage detection,the AC voltage sensors are avoided.By independent controlling the active and reactive components of parallel-in power,the complex algorithms,including the rotation coordinates conversion and the closed-loop current control,are abbreviated.Instead of the pure integrator,the integrator with saturation limit feedback is applied in the virtual flux-linkage observer to avoid the power calculation error of conventional methods,which causes low system efficiency and worse dynamic performance.Simulative and experimental results prove the correctness and feasibility of the proposed method.
What problem does this paper attempt to address?