Plume Centerline Temperature Distribution of Rectangular Pool Fires

Zhi-bin CHEN,Long-hua HU,Ran HUO,Wei PENG,Shi ZHU
DOI: https://doi.org/10.3321/j.issn:1006-8740.2009.03.011
2009-01-01
Abstract:Rectangular 0.5 m2 pool fires with the different aspect ratios of 1, 1.33 and 3 were burned. The mass loss rate of fire and the centerline temperature distribution of plume were measured. Based on image processing by image analyzing program, maximum continuous flame height and maximum flame height were estimated. The centerline plume temperatures were then predicted by Hasemi's model and further compared with the measured values in the experiments. It was shown that as the aspect ratio of pool fire increased, the deviation between the predicted and measured values was shown to increase; When the aspect ratio was equal to 1, the predicted values were close to the measured one; when the aspect ratio was 1.33 or 3, the predicted and measured values showed the similar variation trends, but their deviation exceeded 5%.
What problem does this paper attempt to address?