Study on Flame Pulsation of Pool Fires in Closed Compartments

黎昌海,吴迎春,陆守香,陈兵,胡靖,袁满,周洋
DOI: https://doi.org/10.3969/j.issn.0253-2778.2010.04.009
2010-01-01
Abstract:A series of experiments on heptane pool fires were conducted in a closed compartment without vents with the inner dimensions of 1 m(L)×1 m(W)×0.75 m(H),focusing on flame pulsation characteristics.Different pools with the diameters of 0.100,0.141,0.200 and 0.300 m were investigated.Based on the fact that pulsation frequency of flame bottom area equals that of flame height,a method using flame bottom area was proposed to determine flame pulsation frequency and applied to pool fires in closed compartments with ceiling jet flames.The results show that the variation of flame pulsation frequency is small,and the flame pulsation frequency is smaller than those predicted by empirical equations developed for burnings in free atmosphere while it fits well with the scaling relationship St=0.26 Fr-0.532,and the expression of f=1.33D-0.5 is appropriate in describing the relationship between the flame pulsation frequency and pool diameter.
What problem does this paper attempt to address?