Design of Grading Rings for 1000kV AC Composite Insulator
Xing-ming BIAN,Fu-zeng ZHANG,Li-ming WANG,Zhi-cheng GUAN,Lai WANG,Yong CHEN,Xue-wei BO,Gui-qing REN
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.05.007
2009-01-01
Abstract:The electric field strength along the composite insulators should be restricted to maintain at a reasonable range. We adopted the finite element method to calculate the electric field and potential distribution along composite insulators as well as design the grading rings for the 1000 kV UHVAC transmission lines by the domain decomposition method according to the features of the composite insulator. The three-dimensional (3D) model of 1000 kV transmission lines with tower configuration and conductors were established by using the ANSOFT software. The effect of the corona ring for improving the electric field distribution on the composite insulator was investigated by changing the parameters of the corona ring,such as the ring radius,radius of the ring tube,and the position of the ring in its vertical plane. The approved parameters of the corona ring were gained in terms of controlling the electric field to be acceptable,and the optimized parameters of the grading ring were verified in the 3D model.The results indicate that the maximum electric field around the sheath,metal fitting and the grading ring are controlled to be satisfactory,and the potential distribution along the insulator becomes more uniform. The corona and RIV tests show the corona inception voltage and radio interference voltage of the fittings and corona rings can well meet the national standards.