On the Relationship Between Internal Pressure and Permittivity in the Interrupter of VCB
FAN Xing-ming,LIU Xu-dong,FAN Jian-rong,HE Jia-min,HUANG Zhi-chao,ZHANG Xin,LI Zhen,LIU Hua-dong,SHI Wei-jian,ZHAO Guang-zhou
DOI: https://doi.org/10.3969/j.issn.1002-0322.2012.04.008
IF: 4
2012-01-01
Vacuum
Abstract:Vacuum Circuit Breaker(VCB) is a typical medium voltage distribution switch,and the internal pressure in the vacuum interrupters affects significantly the working quality and life of them.With the development of national smart power grids and the maintenance system based on reliability,on-line condition monitoring of internal pressure in the vacuum interrupters becomes a new requirement of intelligent VCBs.Coupling capacitance sensor is one of the domestic on-line monitoring methods which is achieved by detecting the potential of vacuum interrupter shield Uc,and Uc is closely related to the permittivity er of the dielectric under the internal pressure of the vacuum interrupter.In this research,the relationship between the internal pressure P and er was studied,and the expression of P and er was concluded for dry air condition,which provided the research foundation for further analysis of the relationship between internal pressure P and potential of vacuum interrupter shield Uc.And theoretical support for the practical technology of coupling capacitance sensor was also provided.