The performance analysis and optimization of helium cryogenic cooling system with reverse Brayton cycle for cold neutron source

Feng Yu,Yanzhong Li,Erfeng Chen,Jia Xu
DOI: https://doi.org/10.3321/j.issn:1671-4512.2007.09.012
2007-01-01
Abstract:By the method of exergy analysis and conservation of energy, the performance of reverse Brayton cycle based on helium cryogenic cooling system, of cold neutron source was analyzed. Some effect factors on the exergy efficiency of cycle and the exergy loss of components such as compression ratio of compressor, isentropic efficiency of expander, cold energy loss, and temperature difference in heat exchangers are discussed. The influence regularities of those factors on the cycle performance are obtained. In order to optimize the cycle performance, some methods are recommended in this paper, i.e. decreasing cold energy loss or the temperature difference of heat transfer in heat exchangers, furthermore increasing the compression ratio of compress and the isentropic efficiency of turbo-expander or improving uniform distribution of helium gas in heat exchangers are also efficient ways. As an example, a cycle with a pre-cooling unit by turbo-expander is preliminary designed. It is found that the exergy efficiency is significantly improved by 24% comparing with the basic cycle.
What problem does this paper attempt to address?