Numerical Simulation of Mixed Convections

CHEN Xiaochun,LIN Guanjing,ZHOU Xiang,ZHU Yingxin,WANG Yuan
DOI: https://doi.org/10.3969/j.issn.1001-246x.2007.01.005
2007-01-01
Abstract:A(v′~(2))-f model,a k-emodel and an indoor zero equation model are adopted respectively to simulate mixed convections which are typical in ventilation and air conditioning systems.It indicates that there is a separated vortex near the ventilation inlet,and the accuracy for predicting this vortex is a critical factor in the simulation.The separated vortex dimension obtained by experiments is between the values calculated by the(v′~(2))-f model and the indoor zero equation model,while the dimension predicted by the k-e model is a bit smaller.The results predicted by the indoor zero equation fit experimental results best.However,it is not in general from the view of model structure.For calculating temperature field the(v′~(2))-f model is better than the indoor zero equation model,and the k-e model is the worst among the three.
What problem does this paper attempt to address?