A Filtering Algorithm for Eliminating Effect of Transient Component and Its Application on Fault Location

LIANG Yuansheng,WANG Gang,LI Haifeng
DOI: https://doi.org/10.3321/j.issn:1000-1026.2007.22.017
2007-01-01
Abstract:During the fault transient process,the accurate extraction of power-frequency components is affected by the decaying dc and other transient components existing in the transient voltage and current signals.This paper proposes a novel filtering algorithm to extract the accurate fundamental and integer harmonic frequency component by means of a set of linear equations,which is transformed from a non-linear equation representing the error in discrete Fourier transform affected by decaying dc.Meanwhile,by analyzing the discrete integral error,a correctional scheme is proposed.Extractions from several typical signals and analysis of the frequency response characteristics prove that the proposed algorithm is accurate and stable and has the anti-interference ability for non-integer harmonic frequency component.Extensive tests of fault location show that the algorithm can efficiently improve the precision of fault location during the transient process.
What problem does this paper attempt to address?