Experimental research and optimization of operation mode of solar-powered air-conditioning system

Xiaoqiang Zhai,Ruzhu Wang,Qiang Ma
2006-01-01
Abstract:A solar-powered adsorption air-conditioning system was designed. The operation performance under typical operating mode in summer of Shanghai was studied, which included temperature variations of solar collector arrays and adsorption chillers as well as refrigerating output variations of the system. The experimental results of the system under typical working condition showed that the average refrigeration output of solar-powered air-conditioning system was 15.31 kW during operation of 8 hours; moreover, the maximum exceeded 20 kW. Then the operation mode of the system was optimized by means of variance analysis. It was concluded that the heat consumption and refrigeration output of solar-powered air-conditioning system was optimized by maintaining an identical phase contrast of 540 s between two adsorption chillers. Thereafter, the whole system realized efficient and stable operation by the balance of heat consumption and refrigeration output.
What problem does this paper attempt to address?