Magnetic Force Computation for the Electric Arc of Parallel Gap Lightning Protection Device on Overhead Transmission Lines

GU Shan-qiang,HE Jin-liang,CHEN Wei-jiang,XU Guo-zheng
DOI: https://doi.org/10.3321/j.issn:0258-8013.2006.07.026
2006-01-01
Abstract:The parallel gap lightning protection device (PGLPD) is installed on overhead transmission lines to protect insulator strings against being burnt by power frequency electric arc when the lines meet lightning strokes or power frequency flashover of insulator. The electric arc is driven to move by the combined magnetic force produced by the current flowing through overhead transmission lines, the PGLPD, the tower and the arc itself. The magnetic force determines the direction and velocity of the arc’s movement, therefore determines whether the insulators are efficiently protected or net against being burnt by the arc. Taking the actual high voltage transmission lines into account and based on a practical arc model, a practical procedure is developed to compute the magnetic force of the arc. The PGLPD for 110 kV overhead transmission line are computed and analyzed as an example, and the results have a good consistency with the experimental results. The research will lay the foundation for optimally design the PGLPD.
What problem does this paper attempt to address?