Study on Introducing Radiant Energy Signal for Optimized Oxygen Control in Furnace

LUO Zi-xue,LIANG Pei-lu,ZHOU Huai-chun,CHEN Shi-he
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2006.23.018
2006-01-01
Abstract:Test method of combustion is strongly restricted by combustion behavior in coal-fired power plant boiler furnace. The alternation of coal quality or quantity can be detected transiently, and the change of burning rate can also be judged by radiant energy signal. Traditional combustion control strategy has been meliorated by inducing radiant energy signal (E) into oxygen control circuit. Through modification and in-situ operation on a 300 MW unit of Shajiao A power plant, the control property under the optimized air/coal ratio can always hold the E in high-level and response combustion condition correctly, the new industrial scheme is proved to be practical and economical.
What problem does this paper attempt to address?