Combined Variable Air Volume System

赵加宁,郭骏
DOI: https://doi.org/10.3321/j.issn:0367-6234.2004.12.037
2004-01-01
Abstract:The analysis of air-conditioning load and outdoor enthalpy of large department stores under eight typical climates in China indicates that in transition time, there exists a fairly long period, in which outdoor enthalpy is lower than indoor enthalpy, but water chillers are still used to cool supply air because outdoor air volume has reached its highest limit. It is suggested to largely increase outdoor air volume, not conditioned and designed as an independent subsystem. It combines with conditioned all air subsystem and constitutes a Combined Variable Air Volume System (CVAV). According to the human comfort index PPD, maximum and minimum air volume the system needs are calculated for 8 different climates. When conditioned air subsystem is designed as CAV or VAV and outdoor air as combination of VAV+CAV or VAV+VAV, calculation shows that energy saving can be as high as from 10% to 36.6% in comparison with conventional CAV system.