Modeling of Variable Speed Compressors

邵双全,石文星,李先庭,陈华俊
DOI: https://doi.org/10.3321/j.issn:1000-0054.2004.03.028
2004-01-01
Abstract:The numerical analysis of the variable speed compressor is the core part of air conditioner models used for performance analyses and optimization. The accuracy and versatility of the model was improved by a the map-based model for fitting the performance curves of an inverter compressor. The actual operating performance of the inverter compressor was treated as the performance of an infinite number of constant speed compressors. At the base frequency, the refrigerant mass flow rate and the input compressor power were modeled second-order functions of the condensing and evaporating temperatures. The mass flow rate was a power function of compressor frequency and the power input was a second-order exponential function of the frequency. Experimental data for three compressors were used to validate the model, with the maximum error of the refrigerant mass flow rate of 3. 95% and of the input compressor power of 4. 40%, which are accurate enough for air conditioner simulations.
What problem does this paper attempt to address?