Interference Canceller Based ADF Applied in HVDC System

赵东元,陈建业,王赞基,刘兵
DOI: https://doi.org/10.19595/j.cnki.1000-6753.tces.2004.05.017
2004-01-01
Abstract:Active DC filter (ADF) is one of filtering equipment applied in HVDC. A control strategy based on an interference canceller is proposed in order to overcome the disadvantages of those existing in control strategies of ADF. In the control strategy, the transmission line harmonic current is measured as the feedback signals, while the converter station harmonic current is measured as the system interference. The interference canceller is introduced to improve interference rejection and ensure the stable performance of system without change of characteristic equation. At the same time, the robustness of system can be improved and the response time is decreased, because the design of main controller is simplified. Furthermore, The design rule of interference canceller is detailed. The canceller is composed of several filter banks including band-pass filters, amplifier filters and phase-shifted filters and all that are designed for main characteristic harmonics. The Bode-diagram shows that the impedance-characteristic performance of the canceller is approximate to that of the passive filter. A lot of simulations based on PSCAD/EMTDC and experiments based on a 30 kVA lab system are carried out, and the results can validate the proposed control strategy.
What problem does this paper attempt to address?