Abstract:Eliminating harmonics is one of the key technologies in high voltage direct current (HVDC) transmission systems. This paper analyzes the principle of the active DC filter (ADF) applied in the HVDC system. A composite control strategy, in which the harmonic source current and the compensation current are measured as the compensation object and the feedback signal, is proposed. A filter bank is adopted to compose the approximate inverse system, which is the feed-forward controller in the composite control strategy. Both results of simulation based on PSCAD and experiment on a 30 kVA HVDC system validate that the proposed control system is stable and can eliminate the harmonics, because of the advantages of the approximate inverse system and the absence of the extraction of weak signal from noise. This work has laid foundation for developing industrial equipment in future.
What problem does this paper attempt to address?