RESEARCHES ON HVDC MODELING FOR AC/DC HYBRID GRID WITH MULTI-INFEED HVDC

毛晓明,管霖,张尧,吴小辰,彭显刚
DOI: https://doi.org/10.3321/j.issn:0258-8013.2004.09.012
2004-01-01
Abstract:The problems existed in HVDC modeling of the AC/DC hybrid grid, including over-simplification and improper choice of the model are discussed. The general HVDC modeling methods in stability studies are introduced with the characteristics of three typical models, i.e. the simple model, the response model and the detailed model being analyzed. Digital simulation by NETOMAC program with the south China power grid as prototype is developed to compare the performance and the adaptability of two advanced DC models: the improved response model and the detailed model. For AC/DC hybrid south China power grid with multi-infeed HVDC lines located in the vicinity, the paper discusses the disadvantages of existed HVDC models in the analysis of the AC/DC interactions under large disturbances and the influence of the DC commutation failure to nearby AC/DC systems. On the bases of the above analysis, two feasible research directions for the HVDC modeling, i.e. development of new HVDC phasor model based on the dynamic phasor theory with consideration of the voltage distortion or development of novel digital hybrid algorithm to combine the electromechanical and the electromagnetic models, are proposed. Researches in this paper not only provide reference for the HVDC model choice in stability studies of the AC/DC hybrid grid but also suggest new ideas for researches on the chain DC commutation failures phenomenon that may occur to the multi-neighboring-inverters of a hybrid AC/DC power system.
What problem does this paper attempt to address?