ON-LINE MONITORING SYSTEM ON MEASURING LEAKAGE CURRENT NEAR HV SIDE FOR ELECTRICAL TRANSMISSION LINE INSULATORS

赵汉表,林辉,谢利理,邓正龙
DOI: https://doi.org/10.3321/j.issn:1000-1026.2004.22.017
2004-01-01
Abstract:A on-line monitoring system is presented based on MSP430 to measure insulators leakage current near high voltage (HV) side. The system adopts the parameters such as the maximal peaks, the average peaks and the number of large current pulses of the leakage currents in a period to differentiate the contamination degree of insulators. Hence, a kind of leakage current sensor based on the principle of feedback compensation is described. The design of this structure keeps the sensor holding high linearity. Then the power supply of the on-line device directly obtains from the transmission line through switching and linear DC/DC converter. This paper also analyzes the effect of noise signal on detecting the peaks of leakage currents, and a wavelet transform algorithm is introduced to denoise. Field tests show that it can properly predict the contamination degree of the insulators and offer the pre-alert information when the contamination exceeds the threshold, through analyzing the data acquired from historical real-time records. Thus, the probability of flashover can be reduced and the reliability of the whole power supply system can be improved.
What problem does this paper attempt to address?