Mechanical Response of 16 MnR Tank Exposed to High Temperature (Fire)

邢志祥,蒋军成
DOI: https://doi.org/10.3321/j.issn:1000-0976.2003.05.034
2003-01-01
Abstract:When LPG tanks are exposed to fire, the internal pressure of the tanks will increase quickly and the strength will decline. So, those tanks may cause BLEVE explosion and fire-sphere, threaten people and property safety, and make bad results. Studying the influence of fire on the tanks is very important for preventing and controlling such accidents. The article mainly discusses the mechanics response law of 16 MnR steel usually used in LPG storage tanks. The experiment of mechanical properties of 16MnR steel was first conducted under high temperature. It was obtained the law of the mechanics property indexes (including the stress-strain curve, the yield strength, the tensile strength, the elongation and modules of elasticity, etc.) varying with temperature while the temperature is no more than 600 °C. Also, the pressure response law of the tanks exposed to fire was studied. Using the testing data, the fail pressure of the tanks was analyzed to predict the tank detonation time. The testing results show the strength and elongation of 16 MnR steel decrease obviously under high temperature. The strength and elongation at 600 °C is only 20% - 30% of that at the normal temperature. The tank wall temperature increases rapidly when the tank is exposed to fire. The highest temperature can reach to 600 - 700 °C. The explosion pressure at this case is only 25% of that at the normal temperature, but the internal pressure of the tank at this case will up to twice and more of the normal pressure. The tank will explode in about 10 minutes.
What problem does this paper attempt to address?