Effect of Expansion Device on the Reverse-Cycle Defrost Time of an Air-Source Heat Pump Chiller

黄东,袁秀玲,陈蕴光,张兴群
DOI: https://doi.org/10.3321/j.issn:0253-987X.2003.05.019
2003-01-01
Abstract:An experimental investigation of the influence of the expansion device on the defrost time of an air-source heat pump chiller during the reverse-cycle defrost is presented. A copper tube with the outer diameter of 22 mm is used as the expansion device of the defrost cycle to the heat pump chiller with the nominal heating capacity of 55 kW, and the test results of defrost time are compared with those where the thermal expansion valve (TEV) serves as the expansion device. It is shown that the defrost time for the copper tube is 1.5 min shorter than that for the TEV, and the melting time is 1.3 min shorter. Refrigerant temperature and pressure measurements are also conducted and the refrigerant state of the inlet of the expansion device is revealed. During first one more minutes of melting time and throughout the drain time, the refrigerant entering the expansion device is in a superheated state or two-phase state. Correspondingly, the much larger mass flow rate through the copper tube results in a short defrost time.