Effect of PCM Based Heat Exchanger for Defrosting on Performance of Air Source Heat Pump

胡文举,姜益强,姚杨,董建锴,马最良
2009-01-01
Abstract:Three heating operation modes,i.e.,series heating mode,non-connected heating mode,and connected heating mode,have been presented for a novel phase change material(PCM) based air source heat pump(ASHP)defrosting method and experiments have been carried out to test the effect of the PCM based heat exchanger on the performance of ASHP.Results show that the discharge temperature of the heat pump in non-connected heating mode is about 5 ℃ higher than that in series heating mode,nevertheless,the other parameters such as the suction temperature,discharge and suction pressure are almost unchanged.The discharge temperature and suction temperature in connected heating mode are 30 ℃ and 15 ℃ higher than those in series heating mode,respectively,and the discharge pressure decreases by about 0.2 MPa while the suction pressure almost keeps constant.Among the three operation modes,the series heating mode has the highest energy efficiency ratio(EER),and EER in the connected and non-connected heating modes decreases due to the reduction of refrigerant.However,results also show that EER in connected heating mode can possibly be increased greatly.
What problem does this paper attempt to address?