Sparkover of Rod-Plane Gap for Composite Alternating or Direct/impulse Voltages

王黎明,毛苏春,关志成
DOI: https://doi.org/10.3321/j.issn:1000-0054.2002.03.002
2002-01-01
Abstract:Air breakdown for composite alternating and direct voltages in a rod plane gap at standard atmospheric conditions were studied to understand insulation breakdown in electrical appliances. The test results show that a positive pre stressed DC corona can increase the positive sparkover voltage of the switching impulse and a negative pre stressed DC corona can reduce the positive sparkover voltage of the switching impulse. Smaller rod diameters caused more significant effects since for the same DC voltage, the DC corona pulse current increase with decreasing rod diameter. Photographs show that the positive DC corona reduces the corona activity of the positive streamer and leader formation during a switching impulse, but the negative DC corona has the opposite effect for the pre stressed AC case. The sparkover voltage of the positive impulse without AC pre stressing voltage is always higher than that with AC pre stressing voltage, so the problem is more serious than with DC pre stressing voltage.
What problem does this paper attempt to address?