Experimental Study on Effects of Heat Saving and Heating in an Underground Heat Storage System in Greenhouse
YANG Bo,YAO Xian-zhen,WANG Jian-ping,LI Zhi-xiao,WANG Yong-wei,WEN Le-yuan
DOI: https://doi.org/10.3969/j.issn.1003-188x.2008.01.040
2008-01-01
Abstract:To reduce energy consumption for greenhouse heating, an underground heat storage system in greenhouse was designed based on the plant physiology. Some parameters, including air temperature, humidity, flat temperature inside greenhouse and air temperature, soil temperature in adjacent greenhouse without heat saving and outside greenhouse, were measured during heat saving in the day and heating at night in winter. It was indicated that the flat temperature in the greenhouse after heat saving was 4.8℃ and 4.4℃ higher than that of the greenhouse without heat saving in the clear day and cloudy in winter respectively. In the over cloudy sky,the time of heat saving should be shorten, but the flat temperature was still 2.6℃ higher than that of the adjacent greenhouse owing to the longtime heat saving. In addition, the temperature inside greenhouse with heat saving at night was 3.1℃, 2.0℃, 1.5℃higher than that of the adjacent greenhouse without heat saving respectively and the average temperature difference between inside and outside greenhouse were 3.95℃, 3.21℃, 2.35℃ respectively during heating at night in the clear day, cloudy sky and over cloudy sky in winter, which could at least satisfy 35.7% of the energy consumption for greenhouse heating. So the effects heat saving and heating in the system are significant.