RAPID RECOGNITION AND PROTECTION OF SHORT-CIRCUIT FOR THE DC SYSTEM

赵登福,董继民,张忠元,冯书安,王东
DOI: https://doi.org/10.3321/j.issn:1000-1026.2002.05.009
2002-01-01
Abstract:A novel method that can rapidly recognize short-circuit for the DC system is proposed according to the integrative criterion of loop current and generatrix voltage measured by the HOER sensor. It uses controllable DC breakers instead of traditional fusion, and introduces the theory of three-segments AC protection for the DC system. Applying the same theory, it designs radiate segment one, two, three loops for the DC power supply. This method has the standby power when the DC power supply is lost that caused by the wrong action of segment one breaker and invalidation of segment two and three breaker. The device based on the method is also manufactured. The paper finally analyzes the selectivity, sensitivity, reliability an rapidity of the device. Results of simulations and the on-site operation of the prototype show validity and practicability of the proposed method.