Combustion Control System for CFB

L(U)Zehua,XUXiangdong,CAORenfeng,ZHANGYongzhe
DOI: https://doi.org/10.3321/j.issn:1000-0054.2000.10.019
2000-01-01
Abstract:Frequency domain decoupling control theory was used to develop a new method which uses the CFB combustor temperature as a compensation adjustment to control the CFB combustion controling. This method not only realizes cascade control of the main steam pressure loop, but also overcomes one drawback of CFB that the CFB combustor temperature often fluctuates because of variations of the amount and quantity of coal, primary air and auxiliary air. The new method has been successfully used in a 35t/h CFB.