Harmonic Analysis in AC Excited Generator Systems

SHI Wenhua,WANG Xiangheng,LI Daocheng
DOI: https://doi.org/10.3321/j.issn:1000-0054.1999.03.017
1999-01-01
Abstract:AC excited generator (ACEG) and cycloconverter are principal harmonic sources in ACEG systems. Using multi loop analysis method, spacial gap harmonic magnetmotive force (MMF) and slot effects of the stator and rotor of ACEG are calculated. Circuit oriented model of cycloconverter is developed by adding tube changing mode and group changing mode. The simulating results agree well with experimental results. Based on these, the paper discusses systematically: 1) effects caused by cycloconverter's tube changing and group changing; harmonic comparison between 6 pulse and 12 pulse cycloconverter; 2) effects of spacial gap harmonic MMF, tooth slot of the stator and rotor and short span coefficient of ACEG. At the end of this paper, harmonic restraining measures of ACEG system are presented.
What problem does this paper attempt to address?