APPLICATION OF PULSE BLOCKING PROTECTION METHOD IN STATCOM

Shen Dong,Liang Xu,Han Yingduo,Chen Jianye
DOI: https://doi.org/10.3321/j.issn:1000-1026.1999.12.005
1999-01-01
Abstract:The protection system plays a very important role in STATCOM equipment. The pulse blocking protection method can make STATCOM go into operation immediately after the instant when transient disturbance or system fault disappears. Based on the analysis of the first ±300 kvar STATCOM prototype in China, this paper illustrates the principle of DC side over-voltage in two cases: linear transformer model, transformer model with saturation. The DC side high voltage will damage the capacitor and inverter. A novel assistant circuit to suppress the DC side over-voltage is introduced and it has been successfully employed in ±300 kvar STATCOM prototype. This kind of pulse blocking method is not only suitable for STATCOM, but also for all other FACTS and power electronic devices based on self-commutated voltage source inverter.
What problem does this paper attempt to address?