Influence of Load Models in Sending and Receiving Ends of Henan Power Grid on Tie-line Stability Limit of Sending End
ZHANG Peng-fei,LUO Cheng-lian,MENG Yuan-jing,YAN An-he,ZHANG Yi-ming,FU Hong-jun,JU Ping,ZHANG Heng-xu
DOI: https://doi.org/10.3321/j.issn:1000-3673.2007.06.009
2007-01-01
Abstract:Results of analyzing the dynamic response of the induction motorload and constant impedance load during transient process show that through active power characteristics the load model influences the angle stability.By means of adjusting load models of sending and receiving ends of Henan Power Grid and the simuation of tie-line stability limit,it is pointed out that the tie-line stability limits at sending and receiving ends,which is impacted by transient angle stability,varies with the variation of the proportion of induction motor load to total load and the variation of stator reactance of induction motor,meanwhile,the same load model procreates different influence on transient angle stability while this model is applied in sending or receiving ends.The establishment of load characteristics database of Henan Power Grid and the application of measurement and identification results of load medel are presented,in addition,the analysis and actual measuremnt of load model to be conducted in future are prospected.