Experimental research and calculating model on the composition fractionation during refrigerant mixtures leakage

Xiaoyu Zhao,Lin Shi,LiZhong Han,MingShan Zhu
1998-01-01
Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics
Abstract:Alternative refrigerants have been used in refrigerating and air-conditioning systems due to the phase out of CFC-12, HCFC-22 and R502 etc. Most of them are mixtures. The composition fractionation and thermal performance change during refrigerant leaked out from system must be paid attention. The compositions of mixture THR02 were measured by gas chromatographic analysis. Then we developed a general model to calculate the composition fractionation of zeotropic, near-azeotropic and azeotropic mixtures. The maximum deviations between the calculated compositions arid experimental results are within 5% for the mixture THR02, R407C, R404A and R507. THR02 is a near-azeotropic mixture, it is remain unflammable under the worst case, and the change of system performance only resulted from composition fractionation during refrigerant leakage can be neglected.
What problem does this paper attempt to address?