Energy Consumption Model of Integrated Air Conditioner with Thermosyphon in Mobile Phone Base Station.

Linjun Han,Wenxing Shi,Baolong Wang,Penglei Zhang,Xianting Li
DOI: https://doi.org/10.1016/j.ijrefrig.2013.11.020
IF: 4.14
2013-01-01
International Journal of Refrigeration
Abstract:Data centers and mobile phone base stations (MBS) are consuming more and more energy due to the development of the information communication technology (ICT) industry. The integrated air conditioner with thermosyphon (TACT) was proposed as an efficient cooling device for these spaces, combining vapor compression (VC) refrigeration with a thermosyphon (TS). In this paper, a model to simulate the annual energy consumption of TACT is built and compared with the traditional air conditioner (TAC) in four standard MBSs located in the typical climate zones of China. The results show that the TACT saves 19.1% -28.2% more energy than the TAC, and in hotter regions has a larger energy saving amount but a smaller energy saving rate (ESR). The TS mode works effectively when the mean monthly temperature is 5.4 degrees C-24.5 degrees C. The monthly ESR of TACT in the MBSs of Beijing and Guangzhou is 12.2%-48.6% and 12.1%-45.2% respectively. (C) 2013 Elsevier Ltd and IIR. All rights reserved.
What problem does this paper attempt to address?