Inverse-time Low-impedance Protection Scheme for Microgrids

HUANG Wentao,TAI Nengling,YANG Xia
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2014.01.012
2014-01-01
Abstract:To solve the problem that the conventional distribution-network protections can hardly satisfy the requirements of microgrid without the aid of communication technology, this paper proposed an inverse-time low-impedance (ITLI) protection scheme based on the load impedance. Compared with the traditional inverse-time overcurrent protection, the protection principle, operating characteristics, coordinative method and calculation of setting value of the new protection scheme were extensively investigated based on the structure and fault conditions of microgrids. And the configuration and properties of ITLI were also provided as a reference for the application. Analysis of the impact of fault impedance on ITLI was conducted, and the relevant improvement containing low-voltage acceleration and coordinative acceleration were presented. Independent of communication systems, ITLI protection is immune from the control methods of varied distributed generators, and can meet protection requirement in all operational conditions. A microgrid model was established in PSCAD/EMTDC and the ITLI protection has good performance under different fault conditions and high resistance to fault resistor.
What problem does this paper attempt to address?