Optimal Parameter Of Flame Detection For Outdoor Fire Under Transverse Airflow And Illumination Environments

Dan Zhang,Jun Fang,Jinfu Guan,Jinjun Wang,Yongming Zhang
DOI: https://doi.org/10.1016/j.proeng.2013.08.143
2013-01-01
Abstract:To find the optimal parameter of flame detection for outdoor fire under transverse airflow and illumination environments, experiments were carried out in the standard combustion room and outdoors to investigate the characteristics of four candidate flame parameters (ROB color, oscillation frequency, contour coefficient and area growth rate). Coefficient of Variance (CV) was introduced to analyze the stability of these flame parameters. Experimental conditions included fuels of ethanol and wood cribs, flow velocities of 1.5-8 m/s which can simulate the general wind speed. The study results show that, flame ROB color could be affected by illumination while oscillation frequency and area growth rate could be influenced by airflow, airflow and illumination had little influence on flame contour coefficient and flame contour coefficient is stable and fluctuates within a certain range. tinder the comprehensive comparison of the four parameters and the calculated Coefficient of Variance of them, flame contour coefficient is the optimal parameter for outdoor tire video detection when considering the interference of wind and illumination. The experimental results were also validated by processing the videos of China Central Television Station building tire and a construction-in-process building fire. (C) 2013 International Association for Fire Safety Science. Published by Elsevier Ltd.
What problem does this paper attempt to address?