Modal Analysis of the Low-frequency Oscillation of Power Systems With DFIG-based Wind Farms

LI Hui,CHEN Hongwen,YANG Chao,ZHAO Bin,TANG Xianhu
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2013.28.009
2013-01-01
Abstract:The grid integration of large scale wind power may increase the risks of inter-area low frequency, local power oscillations and the shaft torsion oscillation of the wind turbine. The paper studied the influence of the integration of doubly fed induction generator (DFIG)-based wind farms integration on the low frequency oscillation characteristics of the power system. In order to do small signal stability analysis, a detailed mathematical model was established by considering the effects of wind turbine drive drain, variable pitch control, dynamic models and control strategy of DFIG. By using modal analysis method low-frequency oscillation modes in an IEEE two-area four-machine power system with DFIG-based wind farm were investigated, and the results of the time-domain simulation demonstrated the validity and effectiveness of the model and the corresponding analysis. In the two cases of the constant and variable power flow, the characteristics of local oscillation modes, inter-area oscillation modes, and shaft torsional vibration modes were respectively analyzed under variable operational conditions, including different operation points, different integrated capacity of wind power and whether wind farm participates in reactive power dispatching. The results show that low-frequency oscillation characteristics are closely related to the variation of the power flow, the control strategy and the capacity of wind farm. A suitable coordinated control scheme of synchronous generators could improve the oscillation damping in the condition of constant power flow.
What problem does this paper attempt to address?