Analysis of Influence of Large-Scale Wind Farm Adjacent to Oscillation Center on Damping Characteristics

ZHENG Chao,GE Xing,HUO Chao,LI Huiling,HOU Junxian
DOI: https://doi.org/10.13335/j.1000-3673.pst.2016.2183
2017-01-01
Abstract:After large disturbance,voltage at oscillation center has the lowest amplitude and maximum variation range.Affected by this,significant fluctuations of power of wind farm adjacent to oscillation center will appear,increasing interaction between the wind farm and power grid.In this paper,based on elecyomechanical transient simulation model of doubly fed induction generator (DFIG) provided by GE Company,transient power characteristics of grid-integrated wind farm and influence of different control modes are analyzed in process of low frequency drop and grid voltage Us recovery.According to equal area principle,effect mechanism of three typical Us-Bw trajectories on oscillation damping is revealed,where Bw is equivalent susceptance of wind farm.At last,simulation result obtained from Mengdong delivery system with Guyuan wind farm connected verifies that counterclockwise Us-Bw trajectory can enhance oscillation damping characteristics,and that DFIG voltage feedback regulation can further increase damping capacity.
What problem does this paper attempt to address?