Study on Optimal Operating Mode of a Thermosyphon Heat Exchanger Unit in a Shopping Center

Guoyuan Ma,Feng Zhou,Ting Liu,Liangbing Wang,Xiaolin Zhang,Zhongliang Liu
DOI: https://doi.org/10.1061/(asce)ey.1943-7897.0000126
2013-01-01
Journal of Energy Engineering
Abstract:In order to meet the operating requirements during both winter and summer, a thermosyphon heat exchanger unit used to recover energy from the exhaust air needs to be adjusted for its inclination angle by a regulation mechanism. In this paper, the factors that affect the heat transfer efficiency of the thermosyphon heat exchanger was analyzed and the unit practical operating data in a shopping center was studied. The unit optimal operating mode was acquired due to the influence of the unit inclination angle on the temperature effectiveness under a wide temperature change of the outdoor air. In addition, the inclination angle regulation mechanism uses a programmable logic controller (PLC) to control the unit to work at the optimal operating mode. The unit charged with R410A working fluid worked well and was highly effective.
What problem does this paper attempt to address?