Time-domain Analysis of Dielectric Response in Oil-paper Insulation Using Extended Debye Model

王林,周利军,李先浪,吴广宁,刘君,李延涛
DOI: https://doi.org/10.13296/j.1001-1609.hva.2013.05.009
2013-01-01
Abstract:Dielectric response methods,as a new way to diagnose oil-paper insulation of transformer,have caught much attention recently and been developed from the laboratory studies to the field measurements.The equivalent circuit of the transformer oil-paper insulation system could be represented by extended Debye model,a 50 kV·A transformer was tested by time-domain response measurements in the paper,and the test results were fitted by least squares method,and value of n of extended Debye model was determined by the relative error between measured and fitted values,and electrical insulation parameters were calculated and compared with measured values.Results showed that the time domain response method could effectively assess the moisture content and the insulation condition of transformer oil-paper insulation.
What problem does this paper attempt to address?