A failure model for oil-immersed transformer based on load factor and equipment inspection information

Xiang Zhang,Zitong Song,Zhihui Yang,Qin Zhou,Chuangxin Guo
DOI: https://doi.org/10.13335/j.1000-3673.pst.2013.04.019
2013-01-01
Abstract:To establish a failure model for oil-immersed transformer to synthetically reflect unrepairable failure caused by permanent aging and repairable damage, it is proposed that through constructing the relation between equipment health index and equipment expected lifecycle, the health index (HI) is regarded a parameter to be led into aging failure model to built a new model, i. e., the Arrhenius-Weibull-HI model, to characterize failure rate in the angle of aging development and state estimation. In the analysis on example. It is put forward that when historical data is complete, parameters of the Arrhenius-Weibull-HI model can be fitted by Levenberg- Marquardt method; when the equipment inspection information is not included in historical data, the approximate solution of parameters to be fitted can be obtained by non-sequential Monte Carlo method. The fitting results from calculation example show that the proposed model possesses the ability to characterize actual failure rate.
What problem does this paper attempt to address?