A study of transformer winding vibration using a laser doppler vibrometer

Jing Zheng,Jie Pan,Hai Huang
2012-01-01
Abstract:Many reported transformer failures are due to failures in the windings. Investigation of the behaviours of windings under different failure modes has become a focus for research into fault diagnosis of power transformer windings. In this paper, a laser Doppler vibrometer (LDV) is used to study the winding vibration of a single-phase disk-type power transformer with various causes of failure, such as loosening of winding clamping pressure and removal of insulation blocks on the winding. The results demonstrate that these causes can be identified and characterized by the pattern of surface velocities due to winding vibration. The winding's vibration pattern displays a significant change as the winding clamping pressure gradually decreases. Missing or shifting insulation blocks often lead to a rise in winding vibration and a change in the vibration pattern. The obtained spatial distribution of transformer winding vibration is useful for understanding the details of transformer vibration and for future study of the interaction between the winding and the transformer tank.
What problem does this paper attempt to address?