The Properties of Space Charge in Oil-Paper Insulation During Electrical-Thermal Aging

Sicheng Wu,Jian Li,LinJie Zhao,Yan Wang
DOI: https://doi.org/10.1109/ichve.2012.6357125
2012-01-01
Abstract:Valve windings of converter transformer withstand pulsating voltages. In order to reveal the relationship between the properties of space charge and electrical-thermal aging of oil-paper insulation in converter transformer, this paper did the electrical-thermal aging test at 70 °C under 7.6kV pulsating DC voltage and obtained the samples of different aging time. The internal space charge injection and accumulation properties of aged samples under 20kV/mm and 30kV/mm DC electric field was measured and analyzed by the Pulsed Electro-Acoustic (PEA) method. The results showed that homo-charges injection still occurs at both electrodes in the electrical-thermal aging samples. Aged oil-paper insulation was dominated by negative charge injection as the stressing time increases, which directly cause hetero-charge accumulation in the vicinity of the anode, and homo-charge accumulation near the cathode. It could help explain the reason of the electrical-thermal aging lifetime of oil-paper in sulation is obviously shorter than the electrical or thermal aging. In addition, the longer the aging time, the more the total charge accumulated in the samples.
What problem does this paper attempt to address?