Research on Grid-connected Technology of Power Transfixion Line of High-speed Dedicated Passenger Railway

CHEN Li,CHEN Jin-cao,GAO Guo-qiang,ZHOU Li-jun,LIU Dong-lai,WU Guang-ning
DOI: https://doi.org/10.3969/j.issn.1001-8360.2012.10.005
2012-01-01
Abstract:Power transfixion lines are the key power lines to feed the communication systems of high-speed railway lines,which play a significant role in guaranteeing safe operation of high-speed trains.Power transfixion lines are constrained by superior power systems in reliability to a large extent,and they are featured by presence of large capacitance and relatively unreliable insulation level and lightning protection.There have been disputes whether power transfixion lines are able to be synchronized or not.Study on this issue has seldom been made.In this paper,the principle and safety requirements of grid-connected technology of power transfixion lines were analyzed.The circuit model of power transfixion lines was established on the basis of the datameasured on the site of the Hangzhou-Shenzhen Dedicated Passenger Line.Transient simulation of grid-connected processes of power transfixion lines Grade 1 was conducted under the condition that voltages at distribution substations were given phase difference and amplitude difference.The results show as follows:The voltage phase differences of distribution substations should be limited within-13°~13° and the range of the amplitude ratios within 80%~120%;theoretical basis is provided for grid-connected technology of power transfixion lines.
What problem does this paper attempt to address?